Product Details:
|
Conductor Core: | Copper | Insulation Material: | Cross Linked Polyethylene (XLPE) |
---|---|---|---|
Outer Sheath Material: | XLPE | Armoured Type: | Armoured Or Unarmored |
Cross Section Area: | 0.75mm2 To 1000mm2 | Standards: | IEC60502, GB/T12706, VDE, UL |
Colour: | Customized | Application: | Construction, Power Station |
High Light: | cross linked polyethylene wire,cross linked polyethylene cable |
3 Core Xlpe Power Cable Copper Conductor Medium Voltage Armored Ground Wire
The maximum operating temperature of cores shall not exceed 90 ℃ when the cable is used for long perod.
The temperature of cores shall not exceed 250 ℃ at short circut for S seconds. The amlient temperature should
not be below O℃ during installation.
The permissible bending radirs for cable shall be the permissible bending radius for cable shalbecomplied .
with the regulation as below:
For single-core No armoured cable:R>20(D+d) ±5% For multi-core:R>15(D-d)±5%
Armouredd cable:R>15(D+d)±5% For multi-core:R>12(D+d)±5%
Where:R-bending radius(mm) D-overall diameter of the cable(mm)
d-diameter of conductor(mm)
The single core cable of using in AC circuit shall be without armor or with steel wire armour an shall not be
laid in magnetic ducts.
3 Core Copper Conductor Medium Voltage Armoured XLPE Insulated Power Cable
tem | Single core | Three cores | ||
Non armor | With armor | Non armor | With armor | |
Min bending radius during installation | 20D | 15D | 15D | 12D |
Near joint box or cable terminal, bending with care and use templet |
15D | 12D | 12D | 10D |
Note:D is the diameter of cable |
ype | Designation | Applications |
YJV |
Copper conductor,XLPE insulated,PVC sheathed power cable |
For laying indoors,in tunnel or cable trench,unable to bear external mechanical forces.Single core cable is not allowed to laid in magnetic duct. |
YJLV |
Aluminum conductor,XLPE insulated,PVC sheathed power cable |
|
YJY |
Copper conductor, XLPE insulated,PE sheathed power cable |
|
YJLY |
Aluminum conductor, XLPE insulated,PE sheathed power cable |
|
YJV22 |
Copper conductor,XLPE insulated,steel tape armoured,PVC sheathed power cable |
For laying indoors,in tunnel in cable trench,or direct in ground,able to bear external mechanical forces.Single core cable is not allowed to laid in magnetic duct. |
YJLV22 |
Aluminum conductor,XLPE insulated,steel tape armoured,PVC sheathed power cable |
|
YJV23 |
Copper conductor,XLPE insulated,steel tape armoured,PE sheathed power cable |
|
YJLV23 |
Aluminum conductor,XLPE insulated,steel tape armoured,PE sheathed power cable |
|
YJV32 |
Copper conductor,XLPE insulated,steel wire armoured,PVC sheathed power cable |
For laying indoors,in tunnel cable trench,well or direct in ground,able to bear external mechanical forces and certain pulling force. |
YJLV32 |
Aluminum conductor,XLPE insulated,steel wire armoured,PVC sheathed power cable |
|
YJV33 |
Copper conductor,XLPE insulated,steel wire armoured,PE sheathed power cable |
|
YJLV33 |
Aluminum conductor,XLPE insulated,steel wire armoured,PE sheathed power cab |
3 Core Copper Conductor Medium Voltage Armoured XLPE Insulated Power Cable