Dear David /Betty More I appreciate you is less . Both of you’re amazing . Huanghecables is blessed to have Sales people like both of you Both of you’re most welcome to visit us in India whenever you’re planning.. Would you mind taking 1-2 Sales class with our Teams in India J I also appreciate you accepting such a small quantity

—— Anuj

Your guys are amazing ! Thanks for your good quality cable.

—— Munish

I'm Online Chat Now

Unarmoured / Armoured XLPE Copper Cable Pvc Power Cable Fire Retardant

Unarmoured / Armoured XLPE Copper Cable Pvc Power Cable Fire Retardant
Unarmoured / Armoured XLPE Copper Cable Pvc Power Cable Fire Retardant Unarmoured / Armoured XLPE Copper Cable Pvc Power Cable Fire Retardant

Large Image :  Unarmoured / Armoured XLPE Copper Cable Pvc Power Cable Fire Retardant

Product Details:
Place of Origin: China
Brand Name: Huanghe
Certification: ISO CCC OHSAS
Model Number: YJV YJV22 YJV32
Payment & Shipping Terms:
Minimum Order Quantity: 200
Packaging Details: Wooden drum
Delivery Time: 5-8days
Payment Terms: L/C, T/T, Western Union
Supply Ability: 50000meter per week

Unarmoured / Armoured XLPE Copper Cable Pvc Power Cable Fire Retardant

Description
Application: Power Station,indoor Or Outdoor Conductor Material: Copper Or Aluminum
Insulation Material: PE/PVC/XLPE Jacket: PVC FEP PFA TEFLON PU XLPE TPU TPE TPEE
Standard: IEC60502,BS IEC ASTM DIN Rated Voltage: 600V,1000V
High Light:

cross linked polyethylene wire

,

xlpe insulated wire

Unarmoured / Armoured XLPE Copper Cable Pvc Power Cable Fire Retardant

 

Applications of IEC 60502 XLPE Insulated Cable


IEC60502-1 XLPE Cable are used for electricity supply in low voltage installation system, IEC60502-1 XLPE Cables are suitable for installation in indoors and outdoors, in cable ducts, under ground, in power and switching stations, local energy distributions, industrial plants, where there is no risk of mechanical damage.

 

Construction of IEC60502-1 XLPE Cable

1. Conductors

The conductors shall be either of Class 1 or Class 2 of plain or metal-coated annealed copper or of plain aluminium or aluminium alloy, or of Class 5 of plain or metal-coated copper in accordance with IEC 60228.

2. Insulation

XLPE material and thickness shall be as per IEC 60502 or BS 5467 rated for 90°C continuous operation.

3. Assembly / Inner Covering

The inner coverings may be extruded or lapped. For cables with circular cores, except cables with more than five cores, a lapped inner covering shall be permitted only if the interstices between the cores are substantially filled. A suitable binder is permitted before application of an extruded inner covering. The material is compatible with the insulating material,The materials used for inner coverings and fillers shall be suitable for the operating temperature of the cable and compatible with the insulating material.For halogen free cables, the inner covering and fillers shall also be halogen free compound.

4. Armour

Aluminum/galvanized steel/steel wires applied helically over the Inner Covering as per IEC 60502-1, or double aluminum/steel tapes and copper/tinned copper wire can also be manufactured upon request.

5. Outer Sheath


Outer sheath shall be of extruded PVC Type ST1/ST2 as per IEC 60502-1, Polyethylene type ST3/ST7, Halogen free compound ST8, Polychloroprene, chlorosulfonated polyethylene or similar polymers, type SE1 are also available on request.

6. Fire Performance of Cable Sheaths


Cables can be supplied with special flame retardant PVC outer sheath to comply with the flame test requirements of IEC 60332-3-22, IEC 60332-3-23 and IEC 60332-3-24, Halogen Free material comply to IEC60754-1/2 and IEC 60684-2.

 

Unarmoured & Armoured XLPE Insulated PVC Sheath Power Cable XLPE Copper Cable

 

Low Voltage Power Cable Cu- conductor, XLPE Insulated, PVC Sheathed (Unarmoured) 3 core

 

No.cores x
cross-sec.
Insulation
thickness

Nominal

Sheath
thickness

Outer Ø
approx.
weight
approx.
Current ratings in air 30℃ Current ratings buried 20℃ maximum DC resistance at 20℃
mm² mm mm mm kg / km A A Ω/km
3×1.5 0.7 1.8 10.1 132 21 28 12.1
3×2.5 0.7 1.8 11.0 171 28 37 7.41
3×4.0 0.7 1.8 12.0 225 37 48 4.61
3×6.0 0.7 1.8 13.1 296 47 61 3.08
3×10 0.7 1.8 15.3 440 64 82 1.83
3×16 0.7 1.8 17.5 638 85 107 1.15
3×25 0.9 1.8 21.0 954 115 138 0.73
3×35 0.9 1.8 23.1 1266 140 165 0.52
3×50 1.0 1.8 23.4 1614 168 198 0.39
3×70 1.1 1.9 27.4 2264 213 242 0.27
3×95 1.1 2.0 30.6 2975 263 290 0.19
3×120 1.2 2.1 34.0 3776 307 330 0.15
3×150 1.4 2.3 38.6 4682 357 371 0.12
3×185 1.6 2.4 43.3 5802 415 418 0.10
3×240 1.7 2.6 48.1 7437 498 485 0.08
3×300 1.8 2.8 52.2 9313 575 548 0.06

 

Unarmoured & Armoured XLPE Insulated PVC Sheath Power Cable XLPE Copper Cable

Unarmoured / Armoured XLPE Copper Cable Pvc Power Cable Fire Retardant 0

 

 